AHU从洁净室抽取回风和/或室外新风,通过过滤器(如HEPA/ULPA)去除颗粒物,通过加热和冷却盘管调节温度,通过加湿器/除湿器控制湿度。风机将处理后的空气通过风管循环送回洁净室,维持所需的环境条件。
| 参数 | 典型区间 | 选型说明与越界后果 |
|---|---|---|
| 风量 | 1000–50000 m³/h | Select based on cleanroom class and room volume.ISO 580 |
| 静压 | 300–2000 Pa | Must overcome duct and filter resistance.ISO 580 |
| 制冷量 | 10–500 kW | Determines sensible and latent heat removal.EN 1886 |
| 制热量 | 5–300 kW | For winter or reheat conditions.EN 1886 |
| 加湿量 | 5–200 kg/h | Maintains cleanroom relative humidity.EN 1886 |
| 过滤效率 | H13–H14 HEPA | H13 for ISO 5–8, H14 for ISO 3–4.EN 1822 |
| 温度控制精度 | ±0.5 °C | Tighter tolerance for critical processes.EN 1886 |
| 湿度控制精度 | ±3 % RH | Critical for semiconductor and pharma.EN 1886 |
| 电源电压 | 380–480 V AC | Three-phase, 50/60 Hz.IEC 60038 |
| 功耗 | 5–150 kW | Includes fan, cooling, heating, controls.EN 1886 |
| 工作温度范围 | -10–50 °C | Ambient conditions for AHU installation.EN 1886 |
| 工作湿度范围 | 10–90 % RH | Non-condensing.EN 1886 |
| 防护等级 | IP54–IP55 | IP55 for outdoor installation.IEC 60529 |
| 箱体材质 | 304 SS | Stainless steel for corrosion resistance.ASTM A240 |
区间为行业参考值,供询价时圈定范围用,不构成供应商承诺。下单前请向法人制造商核实每一项数值与标准。
诱因 → 失效模式 → 工程缓解
| pressure: | 静压能力高达 2000 Pa |
| flow rate: | 500-50,000 CFM(可根据风机配置调整) |
| temperature: | 15-30°C(典型工作范围),-10 至 50°C(扩展范围) |
| filtration efficiency: | MERV 13 至 HEPA H14(适用于洁净室应用) |
2 家企业把这个产品列在自己的产品线里。卡片上的公司数据摘自各家官网,每张卡都注明这条关系的依据来自哪里。
制造商列表用于前期研究和供应商能力理解,不代表认证、排名或交易担保。
不是客户评论,也不是实时热度。以下维度用于前期 RFQ 准备和供应商评估。
这些分值是采购评估维度示例,不代表真实客户评分、具体国家买家反馈或实时询盘。
AHU调节和循环空气,以维持温度、湿度、过滤和压力在指定范围内,确保敏感制造工艺所需的洁净环境。
选型需基于洁净室等级、房间容积、所需风量、静压、冷热负荷和湿度控制要求。请向制造商提供这些参数以确定合适的型号。
定期维护包括更换或清洁过滤器、检查盘管和风机、检查控制系统,并监测压降和环境参数。请遵循制造商的维护计划。
相关标准包括ISO 580(风量和压力)、EN 1886(热湿性能)、EN 1822(HEPA/ULPA过滤器)、IEC 60038(电压)、IEC 60529(外壳防护)和ASTM A240(不锈钢)。请与供应商核实合规性。
CNFX 是开放目录,不是交易平台或采购代理。工厂资料和表单用于帮助你准备直接沟通。
CNFX 制造商资料、技术分类、公开产品信息和持续合理性检查。
说明目标数量、应用场景、交期和关键技术要求,用于准备 RFQ 或供应商评估。