电流分流器基于欧姆定律(V=IR)工作,其中精确的低电阻元件产生与电流成比例的可测量电压降。电流互感器基于电磁感应:一次绕组中的交流电流产生变化的磁场,该磁场在二次绕组中感应出成比例的电流,通常降至标准水平(例如5A或1A)以供测量。
| 参数 | 典型区间 | 选型说明与越界后果 |
|---|---|---|
| 额定一次电流 | 5–5000 A | Select based on load current; higher values require larger core.IEC 60044-1 |
| 额定二次电流 | 1–5 A | Standard output for meters and relays.IEC 60044-1 |
| 准确级 | 0.1–0.5 | Lower class for metering; higher for protection.IEC 60044-1 |
| 额定负荷 | 2.5–30 VA | Must match connected device impedance.IEC 60044-1 |
| 额定电压 | 0.66–35 kV | Insulation level for system voltage.IEC 60044-1 |
| 频率 | 50–60 Hz | Matching system frequency is essential.IEC 60044-1 |
| 额定短时热电流 | 10–50 kA | Withstands fault current for 1s.IEC 60044-1 |
| 额定动稳定电流 | 25–125 kA | Peak withstand without damage.IEC 60044-1 |
| 绝缘等级 | E–H | Temperature rating of insulation materials.IEC 60085 |
| 工作温度 | -40–85 °C | Extended range for outdoor use.IEC 60068-2-1 |
| 湿度范围 | 0–95 % RH | Non-condensing conditions.IEC 60068-2-78 |
| 防护等级 | IP54–IP65 | Dust and water resistance for enclosure.IEC 60529 |
| 重量 | 0.5–50 kg | Depends on rated current and voltage. |
区间为行业参考值,供询价时圈定范围用,不构成供应商承诺。下单前请向法人制造商核实每一项数值与标准。
诱因 → 失效模式 → 工程缓解
| pressure: | 大气压至1.5巴(非加压应用,因外壳而异) |
| other spec: | 电流范围:1A至5000A(分流器),5A至5000A(电流互感器);精度:±0.1%至±1% |
| temperature: | -40°C至+85°C(典型工业范围,因型号而异) |
2 家企业把这个产品列在自己的产品线里。卡片上的公司数据摘自各家官网,每张卡都注明这条关系的依据来自哪里。
制造商列表用于前期研究和供应商能力理解,不代表认证、排名或交易担保。
不是客户评论,也不是实时热度。以下维度用于前期 RFQ 准备和供应商评估。
这些分值是采购评估维度示例,不代表真实客户评分、具体国家买家反馈或实时询盘。
电流分流器是一个低电阻元件,产生与电流成比例的电压降,用于直流和低频交流测量。电流互感器(CT)利用电磁感应产生一个降低且隔离的电流信号,适用于高交流电流并提供电气隔离。
额定一次电流应匹配电路的最大负载电流,并留有安全裕度。例如,如果负载电流为100 A,则可能适合选择额定一次电流为150 A或200 A的CT。始终咨询制造商的指南并验证实际系统要求。
准确度等级表示CT或分流器在额定条件下的最大允许误差。对于计量,常用等级如0.1、0.2或0.5;对于保护,使用如5P或10P。更高的准确度(数字更小)对于精确计费或测量是必需的。
负载是连接到CT二次侧的负载阻抗(以VA为单位)。它必须与所连接设备(仪表、继电器)的阻抗匹配,以确保准确性能。超过额定负载可能导致误差或饱和。
CNFX 是开放目录,不是交易平台或采购代理。工厂资料和表单用于帮助你准备直接沟通。
CNFX 制造商资料、技术分类、公开产品信息和持续合理性检查。
说明目标数量、应用场景、交期和关键技术要求,用于准备 RFQ 或供应商评估。