当跳闸单元检测到故障条件(过流、短路等)时,它向跳闸电磁铁线圈发送电信号。这使线圈通电,产生磁场吸引柱塞或衔铁。产生的机械运动要么直接释放断路器的锁扣机构,要么激活二次机构,使断路器触头打开,从而中断电路。故障清除且信号移除后,复位弹簧将柱塞复位,以备下次操作。
| 参数 | 典型区间 | 选型说明与越界后果 |
|---|---|---|
| 线圈电压 | 24 ±10% V DC | Standard control voltage; other voltages available on requestIEC 60038 |
| 线圈电阻 | 20–30 Ω | At 20°C; tolerance ±5% |
| 吸合电压 | ≤75% 标称的 | Must be ≤75% of rated voltage for reliable operationIEC 60947 |
| 释放电压 | ≥10% 标称的 | Must be ≥10% of rated voltage to ensure releaseIEC 60947 |
| 工作温度 | -40–85 °C | Extended range availableIEC 60068-2-1/2 |
| 绝缘等级 | F | Class F (155°C) standard; H availableIEC 60085 |
| 防护等级 | IP54–IP65 | IP65 for dusty/humid environmentsIEC 60529 |
| 机械寿命 | ≥100000 次 | Under normal operating conditionsIEC 60947-5-1 |
| 电气寿命 | ≥50000 次 | At rated loadIEC 60947-5-1 |
| 响应时间 | ≤50 ms | Time from energization to contact openingIEC 60947 |
| 重量 | 0.5–1.5 kg | Depends on coil and mounting |
| 安装方式 | M4–M6 螺钉 | Thread size for mounting screwsDIN 912 |
区间为行业参考值,供询价时圈定范围用,不构成供应商承诺。下单前请向法人制造商核实每一项数值与标准。
诱因 → 失效模式 → 工程缓解
| pressure: | 0 至 10 bar |
| other spec: | 线圈电压容差:额定电压的 ±10% |
| temperature: | -40°C 至 +85°C |
不是客户评论,也不是实时热度。以下维度用于前期 RFQ 准备和供应商评估。
这些分值是采购评估维度示例,不代表真实客户评分、具体国家买家反馈或实时询盘。
跳闸电磁铁是一种电磁执行器,它将来自跳闸单元的电信号转换为机械力,以释放断路器的锁扣或触发断开机构,从而在故障条件下断开电路。
标准线圈电压为24 V DC ±10%(符合IEC 60038),线圈电阻在20°C时为20–30 Ω,公差±5%。可根据要求提供其他电压;请务必与制造商确认。
相关标准包括:IEC 60038(电压)、IEC 60947(性能,如吸合/释放电压、响应时间)、IEC 60068-2-1/2(温度)、IEC 60085(绝缘)、IEC 60529(防护)、IEC 60947-5-1(机械/电气寿命)。这些是验证参考,并非认证证明。
请根据您的应用要求检查指定参数(电压、电阻、温度范围、防护等级、寿命循环)。在采购前,请与法定制造商或供应商确认具体型号的值和合规性。
CNFX 是开放目录,不是交易平台或采购代理。工厂资料和表单用于帮助你准备直接沟通。
CNFX 制造商资料、技术分类、公开产品信息和持续合理性检查。
说明目标数量、应用场景、交期和关键技术要求,用于准备 RFQ 或供应商评估。