当接触器断开时,分离的触头产生高温等离子体电弧。灭弧罩通常由绝缘和去离子板制成,将电弧吸入其结构中。这些板将主电弧分割成一系列较小、较短的电弧。这些较小的电弧被板材料冷却,同时释放去离子气体。拉长、分割、冷却和去离子电弧等离子体的综合效应使其电压需求超过系统可用电压,从而导致电弧熄灭。
| 参数 | 典型区间 | 选型说明与越界后果 |
|---|---|---|
| 额定电压 | 690 V AC V | Maximum voltage for arc extinction capabilityIEC 60947-4-1 |
| 额定电流 | 9–630 A | Continuous current rating rangeIEC 60947-4-1 |
| 分断能力 | 6–100 kA | Maximum short-circuit current at rated voltageIEC 60947-4-1 |
| 灭弧时间 | 10–30 ms | Time to fully extinguish arc after contact separation |
| 介电强度 | 2.5–6 kV | Withstand voltage between live parts and groundIEC 60947-1 |
| 绝缘电阻 | ≥100 MΩ | Minimum resistance at 500 V DCIEC 60947-1 |
| 工作温度范围 | -25–+55 °C | Ambient temperature limits for reliable operationIEC 60947-1 |
| 相对湿度 | ≤95 % | Non-condensing at 40°CIEC 60068-2-78 |
| 防护等级 | IP20–IP54 | Protection against dust and water ingressIEC 60529 |
| 材料等级 | Ceramic (Al2O3 ≥95%) | High thermal shock resistance for arc quenchingGB/T 5593 |
| 重量 | 0.05–2.5 kg | Depends on current rating and number of poles |
| 外形尺寸(长×宽×高) | 30×20×15–150×100×80 mm | Varies with rated current and arc chamber design |
区间为行业参考值,供询价时圈定范围用,不构成供应商承诺。下单前请向法人制造商核实每一项数值与标准。
诱因 → 失效模式 → 工程缓解
该产品或部件会出现在以下工业系统、设备或上级产品中。
| pressure: | 大气压至1.5巴(典型外壳),耐受电弧引起的压力冲击 |
| flow rate: | 不适用 |
| temperature: | -40°C 至 150°C(运行),最高 300°C(电弧暴露瞬态) |
不是客户评论,也不是实时热度。以下维度用于前期 RFQ 准备和供应商评估。
这些分值是采购评估维度示例,不代表真实客户评分、具体国家买家反馈或实时询盘。
主要功能是熄灭接触器触头在负载下断开时产生的电弧,防止损坏并确保电路安全中断。
常用材料包括陶瓷(如滑石瓷)、热固性塑料(如三聚氰胺)以及用于引弧板和灭弧栅片的金属板(如钢)。
典型额定电压最高为690 V AC,额定电流范围为9至630 A,依据IEC 60947-4-1。这些为参考范围,需针对具体型号核实。
灭弧罩将电弧分割成较小段,用板材料冷却,并释放去离子气体,增加电压需求,从而使电弧熄灭。
CNFX 是开放目录,不是交易平台或采购代理。工厂资料和表单用于帮助你准备直接沟通。
CNFX 制造商资料、技术分类、公开产品信息和持续合理性检查。
说明目标数量、应用场景、交期和关键技术要求,用于准备 RFQ 或供应商评估。