断路器使用热磁或电子脱扣机构,检测过电流条件并机械地打开触点以中断电路。隔离开关是手动操作的开关,打开时提供可见的空气间隙,确保维护安全。热元件响应长时间过载,而磁元件响应短路电流。电子脱扣器提供可调设置以实现精确协调。当发生故障时,脱扣机构释放锁扣,导致触点分离并熄灭电弧。隔离开关则不是用于中断故障电流;它们仅在电路断电后操作。其可见断开点确认电路已安全隔离,可进行维护工作。
| 参数 | 典型区间 | 选型说明与越界后果 |
|---|---|---|
| 额定电压 | 230–690 V AC | Higher voltages require increased clearance and creepage distances.IEC 60947-1 |
| 额定电流 | 16–630 A | Select based on load and cable size.IEC 60947-1 |
| 分断能力 | 6–50 kA | Must exceed prospective short-circuit current.IEC 60947-2 |
| 极数 | 1–4 P | Choose based on system configuration (single/three-phase). |
| 脱扣曲线 | B, C, D | B for resistive loads, C for inductive, D for high inrush.IEC 60898-1 |
| 额定绝缘电压 | 750 V | Determines insulation coordination.IEC 60947-1 |
| 额定冲击耐受电压 | 6–8 kV | Ensures protection against transient overvoltages.IEC 60947-1 |
| 工作温度 | -25–70 °C | Outside range may affect tripping characteristics.IEC 60947-1 |
| 防护等级 | IP20–IP65 | Higher IP for dusty or wet environments.IEC 60529 |
| 机械寿命 | 10000–20000 次 | Number of no-load operations before failure.IEC 60947-1 |
| 电气寿命 | 1500–6000 次 | Number of operations under load before contact wear.IEC 60947-1 |
| 安装方式 | DIN rail, panel | DIN rail for modular, panel for fixed. |
| 重量 | 0.2–5.5 kg | Affects panel design and mounting. |
区间为行业参考值,供询价时圈定范围用,不构成供应商承诺。下单前请向法人制造商核实每一项数值与标准。
诱因 → 失效模式 → 工程缓解
| pressure: | 海拔0至2000米(标准),环境压力最高至101.3千帕(1个大气压) |
| flow rate: | 不适用 |
| temperature: | -40°C 至 +85°C(工作),-55°C 至 +125°C(储存) |
不是客户评论,也不是实时热度。以下维度用于前期 RFQ 准备和供应商评估。
这些分值是采购评估维度示例,不代表真实客户评分、具体国家买家反馈或实时询盘。
断路器在过载或短路时自动中断电流,提供保护。隔离开关是手动操作的开关,提供可见的断开点,用于维护安全,但它不用于中断故障电流。
额定电流应根据负载电流和电缆尺寸选择。它必须等于或大于正常负载电流,但小于电缆的载流量。请参考IEC 60947-1,并咨询制造商的数据以用于特定应用。
脱扣曲线定义了磁脱扣阈值。B曲线在3-5倍额定电流时脱扣,适用于阻性负载。C曲线在5-10倍时脱扣,适用于感性负载。D曲线在10-20倍时脱扣,适用于高浪涌电流,如电机和变压器。
相关标准包括IEC 60947-1(一般要求)、IEC 60947-2(断路器)、IEC 60898-1(家用及类似装置)和IEC 60529(防护等级)。务必核实具体型号是否符合您应用所需的标准。
CNFX 是开放目录,不是交易平台或采购代理。工厂资料和表单用于帮助你准备直接沟通。
CNFX 制造商资料、技术分类、公开产品信息和持续合理性检查。
说明目标数量、应用场景、交期和关键技术要求,用于准备 RFQ 或供应商评估。