高压套管通过使用多层绝缘材料(通常为瓷、环氧树脂或复合材料)以同心或分级配置布置,控制电场分布。电容分级沿长度均衡电压应力,防止局部击穿。设计确保高压导体与接地舱体结构完全隔离,同时保持密封以控制环境。
| 参数 | 典型区间 | 选型说明与越界后果 |
|---|---|---|
| 额定电压 | 72.5–550 kV | System voltage class determines insulation levelIEC 60137 |
| 额定电流 | 630–3150 A | Continuous current rating for conductorIEC 60137 |
| 工频耐受电压 | 140–680 kV | Dry and wet test valuesIEC 60137 |
| 雷电冲击耐受电压 | 325–1550 kV | BIL rating for insulation coordinationIEC 60137 |
| 爬电距离 | 16–25 mm/kV | Based on pollution levelIEC 60815 |
| 电容量 | 100–1000 pF | Typical for capacitive graded bushingsIEC 60137 |
| 介质损耗因数 | ≤0.005 | At rated voltage and 20°CIEC 60137 |
| 局部放电熄灭电压 | ≥1.2 U_m/√3 | PD level below 10 pC at this voltageIEC 60137 |
| 工作温度范围 | -40–85 °C | Ambient and conductor temperature limitsIEC 60137 |
| 额定压力 | 0.3–0.6 MPa | For oil-impregnated paper insulationIEC 60137 |
| 防护等级 | IP54–IP65 | Outdoor and indoor applicationsIEC 60529 |
| 绝缘材料 | OIP/RIP | Oil-impregnated paper or resin-impregnated paperIEC 60137 |
| 重量 | 150–2500 kg | Depends on voltage and current rating |
区间为行业参考值,供询价时圈定范围用,不构成供应商承诺。下单前请向法人制造商核实每一项数值与标准。
诱因 → 失效模式 → 工程缓解
| pressure: | 最高10 bar绝对压力(真空至正压) |
| other spec: | 电压等级:1 kV 至 800 kV 交流,50/60 Hz;爬电距离按 IEC 60137 |
| temperature: | -40°C 至 +150°C 连续运行,短期可达 +180°C |
不是客户评论,也不是实时热度。以下维度用于前期 RFQ 准备和供应商评估。
这些分值是采购评估维度示例,不代表真实客户评分、具体国家买家反馈或实时询盘。
高压套管通常根据IEC 60137(套管)和IEC 60815(爬电距离选择)进行规定。这些标准定义了试验方法和性能要求。请务必与制造商核实具体标准版本和型号的合规性。
选择取决于系统电压、持续电流、所需耐受电压、基于污染水平的爬电距离以及环境条件。使用目录中列出的参数作为参考范围,并针对您的具体应用与制造商确认。
建议定期检查表面污染、裂纹或泄漏。监测局部放电和介质损耗因数可以指示绝缘状况。遵循制造商的维护指南,并定期验证性能。
常见故障包括因污染或爬电距离不足引起的闪络、局部放电损坏以及过电压或老化导致的绝缘击穿。正确的选择、安装和维护可降低这些风险。
CNFX 是开放目录,不是交易平台或采购代理。工厂资料和表单用于帮助你准备直接沟通。
CNFX 制造商资料、技术分类、公开产品信息和持续合理性检查。
说明目标数量、应用场景、交期和关键技术要求,用于准备 RFQ 或供应商评估。